Call Phone +8618073152920 Hotline: +8618073152920
Call Phone +8618073152920
English
CONTACT US/ CONTACT US
Consumer hotline +8618073152920
Changsha Zoko Link Technology Co., Ltd.

Email:Arvin@niubol.com

WhatsApp:+8615367865107

Address:Room 102, District D, Houhu Industrial Park, Yuelu District, Changsha City, Hunan Province, China

Position:Home >> Download >> All products

All products

NBL-S-THR Soil Moisture and Temperature Sensor Integration

NBL-S-THR Soil Moisture and Temperature Sensor Integration

Check NiuBoL soil moisture and temperature sensor integration with PLCs and data loggers. Compare analog scaling and Modbus channel checks before ordering your system.

Inquiry

Tel/WhatsApp:+8615367865107

Email:Arvin@niubol.com +Nearly 100 partner companies in more than 75 countries. We are committed to providing high-quality, practical products to meet your needs and help you solve problems. Our products comply with international standards and are certified with ISO, CE and RoHS.

Product Details

Quick Answer: NBL-S-THR soil moisture and temperature sensor integration requires two named measurements and the correct ordered output version. Use separate moisture and temperature inputs for analog versions, or decode the temperature word followed by moisture on RS485 Modbus RTU. Apply each channel's own conversion and reject invalid data before passing values to irrigation logic or a remote platform.

NiuBoL NBL-S-THR soil moisture and temperature probe for two-channel acquisition

Select the electrical version before allocating controller inputs

The product family offers RS485, 4-20mA and 0-5V. Confirm the ordered output in the purchase order and wiring schedule. Do not assume every unit provides all outputs simultaneously.

On an analog version, moisture and temperature are separate signals even though they share one probe body. Allocate the appropriate receiving inputs and check their common-reference and isolation arrangements. One input cannot acquire both values simply because the sensor cable contains both outputs.

The RS485 version puts both measurements on the communication pair, so channel identity is established by register position rather than separate signal terminals. The PLC, RTU or data logger must support the matching driver and serial configuration. A device with a socket marked RS485 is not necessarily already programmed to interpret this probe.

ItemNBL-S-THR specificationIntegration requirement
Moisture span / resolution0-100% / 0.1%Keep moisture separate from air relative humidity.
Temperature span / resolution-50 to 100 degrees C / 0.1 degree CApply the offset as well as the span on analog inputs.
AccuracyMoisture +/-3%; temperature +/-0.5 degrees CUse independent acceptance checks for the two quantities.
Power supply / consumption12-24 VDC / approximately 0.3 WProvide external power; verify the voltage at the sensor.
Output choicesRS485 Modbus RTU, 4-20 mA or 0-5 VOrder one defined version and match the receiving circuit.
Analog load limitsCurrent: up to 250 ohms; voltage: at least 1 kohmCheck input impedance and the full connected arrangement.
Operating limits-40 to 80 degrees CDo not interpret the temperature span as the assembly operating range.
Probe protectionIP68Specify suitable field joints and protect exposed transitions.
Cable jacket and supplied lengthConfirm with the ordered versionResolve the actual cable route before approving the installation.

Connect the analog version as an externally powered transmitter

The current-output arrangement uses external power and signal connections; it is not a self-powered two-wire loop instrument. Do not assume a PLC loop supply can replace the indicated wiring. Compare the receiver's active or passive input requirements with the actual transmitter circuit before energizing it.

LeadAnalog version functionRS485 version function
RedSupply positiveSupply positive
Black or greenSupply negative / circuit referenceSupply negative
YellowSoil temperature signalRS485 A
BlueSoil moisture signalRS485 B

Confirm the delivered cable identification before connection, particularly where a preterminated harness or junction box is involved. Isolate power while changing wiring. The same lead color has a different function on an analog and digital version; yellow is not always a temperature signal across the family.

For 0-5 V acquisition, a shared reference error can change the measured signal. For current acquisition, check the specified load and the receiver arrangement rather than adding an arbitrary resistor. If an external shunt is used, include it in the circuit calculation and verify both analog channels before interpreting the soil readings.

Calculate moisture and temperature independently

For the 4-20 mA version, let I be the measured current in mA. Moisture R = (I - 4) / 16 x 100%, while temperature T = (I - 4) / 16 x 150 - 50 degrees C. The temperature offset is essential: its lower endpoint is -50 degrees C, not zero.

For the 0-5 V version, let V be the measured voltage in volts. Moisture R = V / 5 x 100%, while temperature T = V / 5 x 150 - 50 degrees C. These are conversions for the specified spans, not permission to extend the instrument's operating limits.

Electrical test valueMoisture channel resultTemperature channel result
4 mA or 0 V0%-50 degrees C
12 mA or 2.5 V50%25 degrees C
20 mA or 5 V100%100 degrees C

The table is an electrical scale test. It does not describe simultaneous real soil conditions or require heating the probe to an endpoint. A suitable signal simulator can check the receiving scale without exposing the sensor beyond its operating limit. Use the correct test connection and equipment for the input circuit.

Check a midpoint and endpoints in the receiving software. If 12 mA becomes 75 degrees C, the -50 degree offset has probably been omitted. If a voltage midpoint appears near 2.5 rather than 50% or 25 degrees C, the application may be displaying the raw input without the intended conversion.

Cylindrical NiuBoL soil sensing probe and its cable connection

Decode the two RS485 words in their actual order

For the matching NBL-S-THR configuration, read function 03 from zero-based start address 0x0000 with a count of two registers. The first word is soil temperature and the second is soil moisture. Divide valid decoded measurements by ten to obtain the one-decimal values.

Register / conditionMeaningReceiver action
0x0000Soil temperatureApply the confirmed signed-value convention and divide by ten.
0x0001Soil moistureDivide a valid value by ten and label it as moisture percent.
0x7FFF in either measurement wordInvalid or missing measurementFlag unavailable before applying engineering conversion.
Example words 0x00B4 and 0x0110Decimal 180 and 272Temperature 18.0 degrees C and moisture 27.2%.

Do not divide 0x7FFF by ten and report 3276.7 as a genuine observation. Reject that marker first. Distinguish it from a timeout, which means no valid reply arrived, and from a valid zero measurement. Those conditions require different status handling even if the trend chart leaves the same visual gap.

Configure 9600 bps, eight data bits and no parity, and match the delivered one- or two-stop-bit setting. Allow more than 1000 ms between communications. When adding several probes, assign distinct operating addresses using the supported commissioning procedure with one device connected at a time. Do not assume a vendor-specific address command is a standard register write.

Confirm negative-temperature decoding before commissioning a cold site; the positive example above does not prove how a driver handles negative values. Also check whether the controller labels its first holding register as 0 or 1. Use the actual transmitted start address, not only the number displayed in a programming menu.

Check the receiving record before enabling irrigation decisions

Soil temperature adds context for root-zone conditions and seasonal change. Keep it as a separate channel with its own unit and acceptance check rather than treating the combined probe as one value.

Compare moisture response during a known wetting event and compare temperature with a local reference after stabilization. Verify the same values, units and timestamp in the logger and platform.

Use a point name that distinguishes location, depth and quantity. Verify that a gateway preserves the two labels, units and observation time. RS485 Modbus RTU is the local acquisition interface; MQTT, HTTP or another server connection, where required, belongs to the selected gateway and platform configuration.

Test a planned communication interruption. The receiving system should identify unavailable or stale data rather than repeatedly issuing the last moisture value as a new observation. An irrigation controller also needs an agreed response to missing data; the sensor alone does not define valve behavior or a safe fallback.

Unexpected resultLikely integration check
Temperature changes when the moisture test signal changesCheck analog lead assignment, input channel names or digital word order.
Temperature consistently 50 degrees too high in an analog scale testCheck the missing -50 degree offset.
Very large digital values during a faultCheck invalid-marker handling before scaling.
Local values correct, remote values ten times differentCheck whether conversion is absent or applied twice in the export path.
Both channels disappear togetherCheck common power, cable and device communication before treating both sensing elements as failed.

For buried placement and irrigation response checks, use the soil probe installation and acceptance page. Correct arithmetic cannot repair an air gap or an unrepresentative location. Resolve acquisition and soil installation as separate checks so neither problem is hidden by an artificial software offset.

For NiuBoL integration review, provide the ordered output, PLC or logger input type, supply, cable route and two required channel names. Include the expected negative-temperature conditions and server format where relevant. This allows the quotation to include the appropriate acquisition equipment rather than assuming every receiver supports every output.

NiuBoL sensor to data logger and communication system diagram

Project Decision FAQ

Q1. Does soil moisture and temperature sensor integration require two PLC inputs?

Analog versions provide separate moisture and temperature signals, so both require suitable receiving inputs. The RS485 version carries the two quantities digitally on one communication pair, with separate register identities.

Q2. Is the 4-20 mA probe a two-wire loop-powered device?

No. Use its external supply and the specified signal wiring. Review the receiver's input circuit rather than assuming a two-wire transmitter arrangement or a self-powered sensor.

Q3. What does 12 mA mean?

For the stated scales, it means 50% on the moisture channel or 25 degrees C on the temperature channel. Identify the signal before applying a conversion; the same current does not mean the same engineering number.

Q4. Which Modbus value comes first?

The matching two-register sequence starts with temperature at 0x0000 and moisture at 0x0001. Verify this order and the delivered configuration before assigning tags in the receiving software.

Q5. How should 0x7FFF be handled?

Treat it as invalid or missing for the affected channel before scaling. Do not convert it to a large engineering value or replace it with a genuine zero reading.

Q6. Can an electrical simulator accept the complete soil measurement?

No. It checks the receiving input and conversion. The installed probe still needs separate checks of soil contact, temperature comparison and moisture response under a suitable field procedure.

Q7. What is needed to confirm compatibility before ordering?

Send the required output, receiver input specification or Modbus driver details, supply, cable distance and data destination. Identify both required measurements and any relevant negative-temperature conditions so the full acquisition path can be reviewed.

Summary

Reliable soil moisture and temperature sensor integration keeps electrical version, signal identity and conversion aligned. For the NBL-S-THR, verify the analog temperature offset or the two-word Modbus order, reject invalid measurements and confirm both records at the destination. These checks prevent a correctly installed soil probe from becoming an incorrectly scaled control input.

Sensors & Weather Stations Catalog

Agriculture Sensors and Weather Stations Catalog-NiuBoL.pdf

Weather Stations Catalog-NiuBoL.pdf

Agriculture Sensors Catalog-NiuBoL.pdf

Water Quality Sensor Catalog-NiuBoL.pdf

Related recommendations

Tell us your requirements,Let's discuss more about your project,we can do more.

Name*

Tel*

Email*

Company*

Country*

Message


online
Contacts
Email
Top
XNBL-S-THR Soil Moisture and Temperature Sensor Integration-All products-Automatic Weather Stations_Industrial, Agricultural, Water & Environmental IoT Monitoring Solutions—NiuBoL

Screenshot, WhatsApp to identify the QR code

WhatsApp number:+8615367865107

(Click on WhatsApp to copy and add friends)

Open WhatsApp

The WhatsApp ID has been copied, please open WhatsApp to add consultation details!
WhatsApp