Call Phone +8618073152920 Hotline: +8618073152920
Call Phone +8618073152920
English
CONTACT US/ CONTACT US
Consumer hotline +8618073152920
Changsha Zoko Link Technology Co., Ltd.

Email:Arvin@niubol.com

WhatsApp:+8615367865107

Address:Room 102, District D, Houhu Industrial Park, Yuelu District, Changsha City, Hunan Province, China

Position:Home >> Download >> All products

All products

NBL-W-CO2 Sensor 4-20mA Wiring and Scaling Guide

NBL-W-CO2 Sensor 4-20mA Wiring and Scaling Guide

Wire the NiuBoL NBL-W-CO2 4-20mA sensor to a PLC using its 0-5000 ppm scale. Compare current tests, input loading and fault checks before specifying your installation.

Inquiry

Tel/WhatsApp:+8615367865107

Email:Arvin@niubol.com +Nearly 100 partner companies in more than 75 countries. We are committed to providing high-quality, practical products to meet your needs and help you solve problems. Our products comply with international standards and are certified with ISO, CE and RoHS.

Product Details

Quick Answer: For the NBL-W-CO2 0-5000 ppm current-output version, concentration is C = (I - 4) / 16 x 5000, where I is measured in mA. The sensor uses 12-24 VDC and a receiving load of no more than 250 ohms. Confirm its separate power and signal connections from the delivered wiring diagram; a 4-20mA output does not mean the instrument can be wired as a generic two-wire loop-powered transmitter.

NiuBoL NBL-W-CO2 louvered carbon dioxide sensor housing

Confirm the 4-20mA version before wiring the panel

The NBL-W-CO2 is available with current or RS485 output. A PLC current input cannot read an RS485 pair, and changing software scaling cannot convert the interface. Check the instrument label, output option and concentration span before preparing terminals or ordering replacement devices.

Technical specifications

ItemSpecification
Range0-5000 ppm
Accuracy+/-(50 ppm + 3% of reading)
Resolution1 ppm
Supply12-24 VDC
Output4-20mA; RS485 is also listed as an option
Current-loop loadUp to 250 ohms
Cable2.5 m
Environment-10 to 50 degrees C; 0-100% RH
Power0.2 W
ScalingC = (I - 4) / 16 x 5000 ppm

The NBL-W-CO2 V4.0 configuration uses a 0-5000 ppm span. A different span needs a different conversion. Resolution of 1 ppm describes the increment of the result, not an accuracy of 1 ppm.

Connect power and the current signal as separate functions

Positive supply, supply return and current signal are separate electrical connections. The PLC or logger input must be compatible with that powered output arrangement. Identify the input module's passive or active behavior and common terminal before connecting it. Do not combine two powered outputs or assume that a diagram for a two-wire pressure transmitter applies to this sensor.

Complete wiring with power isolated. Check the delivered conductor schedule, terminal numbering and required signal return. Identify each conductor by its assigned electrical function and the supplied wiring diagram; do not rely on color alone. A replacement extension cable can use different colors without changing the electrical function of each conductor.

Measure supply voltage at the sensor while it is operating. The current-output load limit is 250 ohms. A 250 ohm receiver has a 5 V drop at 20 mA, calculated from V = I x R. Include added series loads and interface equipment in the design, but do not infer the permissible circuit from voltage subtraction alone; the transmitter and input module wiring requirements still apply.

Route the signal away from power-switching conductors where practical and follow the site's grounding method. For separate cabinets or different ground potentials, review whether an appropriate signal isolator is required. Cable extension and an isolator are engineering choices to check against supply, load and receiving-input specifications, not automatic accessories for every installation.

Convert current once, using the installed span

Measured currentCO2 concentration for 0-5000 ppm
4 mA0 ppm
8 mA1250 ppm
12 mA2500 ppm
16 mA3750 ppm
20 mA5000 ppm

If the analog module already converts input current to engineering units, do not apply the same conversion again in the HMI. If it supplies raw ADC counts, use that module's documented count range and status information. There is no universal raw-count formula shared by every PLC.

A channel configured as 0-20mA will interpret the live-zero region incorrectly. A 12 mA input also cannot mean 2500 ppm when the ordered span is 0-2000 ppm; on that span it represents 1000 ppm. Keep the range on the sensor label consistent with the PLC scale, HMI tag and any gateway conversion.

For wider monitoring, the current input can belong to a PLC, RTU or compatible data logger. Remote communication is supplied by that acquisition system. The following station diagram illustrates the wider collection path; it does not mean a CO2 sensor alone includes every illustrated instrument or network option.

NiuBoL environmental sensor system diagram with data acquisition and remote transmission

Test the receiving channel before judging the gas measurement

Use an appropriate current source at the receiving input to test the PLC scale, following the input module's procedure. Isolate the transmitter output as required and do not drive a test current into another active current output. Check 4, 12 and 20 mA at the PLC, then confirm the corresponding values at the HMI and stored record.

This test verifies the electrical receiving chain, not the CO2 sensing accuracy. Reconnect the sensor correctly and perform a separate comparison using a suitable reference or calibration method. Moving people close to the inlet can demonstrate a response, but exhaled air is not a traceable span gas and is not a calibration procedure.

The stated accuracy is +/-(50 ppm + 3% of reading). At 1000 ppm, that expression gives +/-80 ppm before considering a comparison instrument and test conditions. A tight control band should account for measurement uncertainty; adding display digits or averaging indefinitely does not remove a systematic offset.

SymptomDistinguishing check
PLC value wrong during current simulationCheck selected input mode, raw-count mapping and duplicate scaling. Inspect HMI conversion if the PLC value itself is correct.
Simulation correct; live reading differs from a referenceCheck air location, comparison timing, sensor condition and reference suitability before changing the PLC span.
Value rises correctly but stops below the upper spanInvestigate receiving load, supply at the device and interface limits. Do not assume low process concentration is the cause.
Zero or out-of-range currentCheck power, wiring and input status. Use the delivered fault behavior; do not silently clamp every fault to valid zero CO2.

Choose an air-sampling point that matches the control task

Correct loop scaling cannot repair a poor location. Avoid direct breath, a dosing outlet, fresh-air diffuser, combustion exhaust or stagnant cabinet unless that local point is intentional. Large spaces may need multiple transmitters.

For occupied-space ventilation, place the instrument where it samples the air relevant to the ventilation zone, not inside a closed control cabinet. A sensor beside an open door or supply-air diffuser can respond to that local stream rather than the occupied space.

For greenhouse enrichment, avoid the immediate dosing plume unless that plume is the intended measurement. Review the reading during a supervised dosing or ventilation change. The controller needs a defined response to sensor failure; concentration trending alone is not a certified personnel-safety system or an independent dosing interlock.

For several analog points, each transmitter normally needs its own receiving channel and identifiable wiring path. Where the project instead needs many addressed sensors on a field bus, compare the RS485 integration arrangement before buying current-output versions. Modbus settings concern that alternative version, not the analog current signal.

Louvered CO2 sensor enclosure for an installed air-monitoring point

Project Decision FAQ

Q1. Is the NBL-W-CO2 current version a two-wire transmitter?

Do not assume it is. This powered-output arrangement has separate supply, return and current-signal connections. Match that arrangement to the receiving input. Confirm the delivered diagram before wiring, especially when the PLC input supplies loop power.

Q2. Can a 250 ohm resistor provide a voltage signal?

A 4-20mA current through 250 ohms develops 1-5 V, not 0-5 V. That resistance reaches the listed load limit. Check the complete circuit and voltage-input requirements before using this arrangement, and do not add the resistor in series with another 250 ohm load.

Q3. What does current below 4 mA mean?

It is outside the nominal measuring span, but the exact interpretation depends on transmitter behavior and input diagnostics. Check power and wiring and apply the specified fault policy. Use a standardized fault-current code only when the delivered instrument explicitly supports it.

Q4. Can a loop test replace calibration?

No. Current simulation checks the receiving circuit and software conversion. Gas calibration or a suitable reference comparison checks the sensing response. Both are needed when the project acceptance requires confidence in the complete concentration channel.

Q5. Can the standard cable be extended?

Review total distance, supply at the sensor, receiving load, electrical noise and outdoor joints before agreeing an extension. Provide the required length with the PLC input details. Do not assume the standard 2.5 m cable specifies a universal maximum installed distance.

Q6. What should an integrator send for a quotation?

Provide concentration span, current-output requirement, supply, PLC or logger input, cable route and number of measurement zones. Describe whether the duty is ventilation monitoring or greenhouse enrichment, and state any reference-check, connector or interface requirements that affect the package.

Q7. Can one sensor represent several rooms or greenhouse compartments?

Only if the air conditions and control objective justify that arrangement. Independently ventilated or dosed zones can need separate points. More precise electronics cannot correct a sensor installed in an air zone different from the one being controlled.

Summary

For this 4-20mA CO2 channel, confirm the output wiring and 0-5000 ppm span, test the receiving input with current simulation, then check the actual air measurement separately. NiuBoL can review the sensor configuration against your PLC input and installation requirements before quotation.

Sensors & Weather Stations Catalog

Agriculture Sensors and Weather Stations Catalog-NiuBoL.pdf

Weather Stations Catalog-NiuBoL.pdf

Agriculture Sensors Catalog-NiuBoL.pdf

Water Quality Sensor Catalog-NiuBoL.pdf

Related recommendations

Tell us your requirements,Let's discuss more about your project,we can do more.

Name*

Tel*

Email*

Company*

Country*

Message


online
Contacts
Email
Top
XNBL-W-CO2 Sensor 4-20mA Wiring and Scaling Guide-All products-Automatic Weather Stations_Industrial, Agricultural, Water & Environmental IoT Monitoring Solutions—NiuBoL

Screenshot, WhatsApp to identify the QR code

WhatsApp number:+8615367865107

(Click on WhatsApp to copy and add friends)

Open WhatsApp

The WhatsApp ID has been copied, please open WhatsApp to add consultation details!
WhatsApp