The Illuminance Lux Sensor Transmitter is a high-performance light intensity measurement device that uses a highly sensitive silicon blue photovoltaic detector as the core sensor. This product features a wide measurement range, excellent linearity, good waterproof performance, easy installation, and supports long-distance transmission. Users can select the appropriate range and output method according to different application scenarios. It is widely used in agricultural green···
Tel/WhatsApp:+8615367865107
Email:Arvin@niubol.com +Nearly 100 partner companies in more than 75 countries. We are committed to providing high-quality, practical products to meet your needs and help you solve problems. Our products comply with international standards and are certified with ISO, CE and RoHS.Product Details
The NiuBoL NBL-W-LUX Illuminance Lux Sensor is designed to measure environmental illuminance in lux for agricultural greenhouses, building automation, urban lighting, environmental monitoring and industrial data acquisition applications.
The sensor uses a silicon blue photovoltaic detector to convert incident light into an electrical measurement signal. It offers a measurement range of 0–200,000 lux, a spectral response of 380–730 nm and a specified measurement accuracy of ±7%.
Available with RS485 Modbus RTU, 4–20 mA or 0–5 V output, the NBL-W-LUX can be integrated with compatible PLCs, data loggers, RTUs and environmental monitoring systems.

Wide Measurement Range: Measures illuminance from 0 to 200,000 lux for indoor and outdoor light monitoring applications.
Photovoltaic Detection: Uses a silicon blue photovoltaic detector with a specified spectral response of 380–730 nm.
Multiple Output Options: Available with RS485 Modbus RTU, 4–20 mA or 0–5 V output configurations.
Industrial Power Supply: DC 12 V or DC 24 V power supply configurations for compatible acquisition systems.
Simple Installation: Two mounting holes allow installation using M4 screws and suitable mounting brackets.
Flexible Cable Configuration: Standard 2.5 m cable, with alternative lengths available according to order requirements.
System Integration: Suitable for integration with compatible industrial controllers, weather stations and agricultural monitoring equipment.
| Parameter | Specification |
|---|---|
| Model | NBL-W-LUX |
| Product Type | Illuminance Sensor / Lux Transmitter |
| Detector | Silicon Blue Photovoltaic Detector |
| Measurement Parameter | Illuminance (lux) |
| Measurement Range | 0–200,000 lux |
| Spectral Range | 380–730 nm |
| Specified Accuracy | ±7% |
| Power Supply | DC 12 V or DC 24 V, According to Ordered Configuration |
| Output Options | RS485 / 4–20 mA / 0–5 V |
| Digital Communication Protocol | Modbus RTU (RS485 Version) |
| Baud Rate | 9600 bps |
| Communication Interval | ≥1000 ms |
| Load Resistance | Voltage Output: ≥1 kΩ Current Output: ≤300 Ω |
| Operating Temperature | −10 to +70 °C |
| Operating Relative Humidity | 0–80% RH |
| Standard Cable Length | 2.5 m |
| Product Weight | 170 g |
Configuration Note: RS485, 4–20 mA and 0–5 V are selectable output configurations. Confirm the required measurement range, supply voltage, signal type and cable length before ordering. For applications requiring a specific ingress protection rating or defined measurement uncertainty, confirm the applicable specifications separately.
An illuminance sensor detects incident optical radiation and converts the detector response into an electrical signal representing illuminance.
Illuminance describes the luminous flux incident on a surface per unit area. Its measurement unit is lux (lx), equivalent to one lumen per square meter.
The NBL-W-LUX uses a photovoltaic sensing element and signal-processing circuitry to provide an output corresponding to the selected illuminance measurement range.
Measurement performance can be influenced by the spectral characteristics of the light source, sensor orientation, contamination of the optical surface and the measurement environment.
Although illuminance sensors, solar radiation sensors and plant-light instruments all respond to optical radiation, they measure different physical quantities.
| Instrument | Measurement Unit | Primary Application |
|---|---|---|
| Illuminance Sensor | lux (lx) | General Light Environment Monitoring |
| Pyranometer | W/m² | Solar Irradiance and Environmental Energy Measurements |
| PAR-Band Irradiance Sensor | W/m² | Irradiance Within the Photosynthetically Active Spectral Band |
| Quantum Sensor | μmol/(m²·s) | Photosynthetic Photon Flux Density (PPFD) |
The NBL-W-LUX is an illuminance instrument. It does not directly measure broadband solar irradiance, photosynthetic photon flux density or daily light integral (DLI).
Lux measurements can support greenhouse light-condition monitoring, particularly when comparing similar lighting environments. However, illuminance is weighted according to human visual sensitivity and is not directly equivalent to the photon flux available for plant photosynthesis.
For crop-lighting research or supplementary lighting systems that require PPFD or DLI, select an appropriate quantum measurement instrument.
The NBL-W-LUX can be supplied with different electrical outputs to match the receiving controller or acquisition equipment.
When using a compatible NiuBoL collector, connect the sensor to the designated input according to the supplied wiring instructions.
For independent system integration, the documented cable identification is shown below.
| Wire Color | 0–5 V Version | 4–20 mA Version | RS485 Version |
|---|---|---|---|
| Red | Power Positive | Power Positive | Power Positive |
| Black (Green) | Power Ground | See Ordered Wiring Diagram | Power Ground |
| Yellow | Voltage Signal | Current Signal | A+ / TX |
| Blue | — | — | B− / RX |
Wiring Note: Confirm the actual output configuration and supplied connection diagram before applying power. The analog current-loop arrangement must match the delivered transmitter and receiving input. Do not assume that all output versions use the same wiring method.
For analog-output versions, the receiving controller converts the electrical signal into the corresponding illuminance value using the configured measurement range.
L = (I − 4) / 16 × Lmax
L = measured illuminance (lux).
I = measured current (mA).
Lmax = upper limit of the selected zero-based measurement range (lux).
L = V / 5 × Lmax
L = measured illuminance (lux).
V = measured output voltage (V).
Lmax = upper limit of the selected zero-based measurement range (lux).
For a 0–200,000 lux configuration, the corresponding ideal analog scaling values are:
| Illuminance | Current Output | Voltage Output |
|---|---|---|
| 0 lux | 4 mA | 0 V |
| 50,000 lux | 8 mA | 1.25 V |
| 100,000 lux | 12 mA | 2.5 V |
| 150,000 lux | 16 mA | 3.75 V |
| 200,000 lux | 20 mA | 5 V |
These values illustrate the nominal electrical scaling and do not represent independently measured calibration results. Configure the receiving system according to the actual ordered measurement range.
The RS485 version of the NBL-W-LUX supports Modbus RTU communication for integration with compatible PLCs, RTUs and industrial data acquisition equipment.
| Communication Parameter | Specification |
|---|---|
| Interface | RS485 |
| Protocol | Modbus RTU |
| Baud Rate | 9600 bps |
| Data Bits | 8 Bits |
| Parity | None |
| Stop Bits | 1 or 2 Bits, Confirm Device Configuration |
| Minimum Communication Interval | 1000 ms |
Before integration, confirm the device address, serial settings, register definitions, data format and illuminance scaling factor for the delivered sensor.
For multiple sensors sharing an RS485 network, use compatible communication settings and unique device addresses.
The sensor itself does not provide independent wireless communication. A compatible data acquisition device or IoT gateway is required for remote data transmission.
Choose the mounting location according to the surface or environment whose illuminance must be monitored.
Avoid unintended shading from mounting poles, nearby equipment or structures unless the shaded condition is part of the intended measurement.
Fix the sensor to a suitable bracket using M4 screws and nuts through its two mounting holes.
Maintain the required observation orientation. For horizontal illuminance monitoring, install the sensing surface in the intended horizontal measurement plane.
Disconnect power before wiring. Connect the supply and signal conductors according to the selected output configuration, then verify the connections before switching on the equipment.
Check the sensor response under different light conditions and confirm that the receiving system displays the expected measurement units and scaling.
A functional light-response test does not establish calibrated measurement accuracy. Where numerical accuracy is critical, use an appropriate reference instrument and controlled comparison procedure.
Monitor changes in the greenhouse light environment, shading conditions and supplementary lighting operation.
Illuminance measurements can provide useful environmental information but should not be treated as direct measurements of photosynthesis, PPFD or crop productivity.
Provide ambient light measurements for building monitoring, lighting management and compatible automatic lighting control systems.
Automatic adjustment of lighting equipment requires an external controller and appropriate control hardware.
Monitor environmental illumination for lighting studies, infrastructure management and integration with compatible street-lighting control systems.
Record local illuminance changes associated with daylight, cloud cover and surrounding environmental conditions.
For solar energy measurements expressed in W/m², use an appropriate solar radiation instrument instead of a lux sensor.
Provide illuminance measurements for industrial environments, laboratories and general environmental observation projects, subject to the required measurement accuracy and applicable operating conditions.
Regular inspection helps maintain representative optical measurements and reliable electrical connections.
| Observed Problem | Possible Cause | Recommended Check |
|---|---|---|
| Reading Is Unexpectedly Low | Dust, Deposits or Unintended Shading | Inspect and Clean the Optical Surface |
| Analog Reading Is Incorrect | Incorrect Input Range or Scaling | Verify Signal Type and Ordered Measurement Range |
| No RS485 Response | Power, Wiring or Communication Configuration | Check Supply, A/B Wiring, Device Address and Serial Settings |
| Reading Remains at Maximum | Possible Over-Range Condition or Signal Processing Issue | Check Light Conditions and Receiving-System Configuration |
Do not disassemble the sensor or clean the optical surface with sharp objects or corrosive liquids. Contact the manufacturer before modifying factory-installed cables or internal components.
Specify the following information when ordering an illuminance sensor:
Product Model: NBL-W-LUX.
Measurement Range: Standard 0–200,000 lux, or another confirmed configuration.
Power Supply: DC 12 V or DC 24 V.
Output: RS485, 4–20 mA or 0–5 V.
Cable Length: Standard 2.5 m or customized length.
Installation Environment: Indoor, greenhouse or appropriately protected outdoor installation.
Receiving Equipment: PLC, data logger, RTU or other compatible acquisition device.
An illuminance sensor measures illuminance, expressed in lux. It describes the light incident on a surface according to a photometric measurement scale.
The standard specified measurement range is 0–200,000 lux, with a spectral response range of 380–730 nm and specified accuracy of ±7%.
No. The NBL-W-LUX measures illuminance in lux. PAR-band irradiance and PPFD require instruments designed and calibrated for those quantities.
Yes. The RS485 version supports Modbus RTU communication for compatible PLCs, RTUs, data loggers and industrial monitoring systems.
The NBL-W-LUX is offered with selectable output configurations. Confirm the required signal type when ordering rather than assuming all outputs are provided simultaneously.
The sensor can be considered for outdoor light-monitoring applications when its operating conditions and installation protection are suitable. Confirm humidity exposure, ingress protection requirements and cable arrangements before deployment.
The sensor provides illuminance measurements. Automatic lighting control requires a compatible controller, configured control logic and suitable electrical switching equipment.
NiuBoL supplies illuminance sensors, solar radiation instruments, agricultural sensors and compatible data acquisition equipment for environmental monitoring and industrial system integration.
For product selection, specify the required measurement quantity, signal interface, installation environment and receiving equipment.
Contact NiuBoL for NBL-W-LUX illuminance sensor specifications, technical support and a project-specific quotation.
Download the instruction manual for technical specifications, installation information, analog output conversion formulas, wiring and RS485 communication details.
Prev:RS485 Modbus Temperature and Humidity Sensor
Next:High-Intelligent All-Project Soil Fertilizer Nutrient Tester
Sensors & Weather Stations Catalog
Agriculture Sensors and Weather Stations Catalog-NiuBoL.pdf
Weather Stations Catalog-NiuBoL.pdf
Agriculture Sensors Catalog-NiuBoL.pdf
Water Quality Sensor Catalog-NiuBoL.pdf
Related recommendations
Multi-Depth Soil Sensor RS485
TDR Soil Moisture Sensor
Pyranometer Solar Radiation Sensors
Soil ph sensor
Tipping Bucket Rain Gauge - ABS and Stainless Steel
Air Temperature and Humidity Sensor
Screenshot, WhatsApp to identify the QR code
WhatsApp number:+8615367865107
(Click on WhatsApp to copy and add friends)