— Blogs —
—Products—
Consumer hotline +8618073152920 WhatsApp:+8615367865107
Address:Room 102, District D, Houhu Industrial Park, Yuelu District, Changsha City, Hunan Province, China
Product knowledge
Time:2025-12-13 11:27:36 Popularity:886
Quick Answer: The 5-in-1 sensor working principle combines individual sensing channels with local signal processing and a shared output. The NBL-W-THPLC measures air temperature, relative humidity, atmospheric pressure, illuminance and CO2 through one RS485 connection. Its shared housing reduces field connections, but it does not measure wind or rainfall. Choose it when these five measurements belong at the same monitoring point; use separate sensors when crop lighting, ventilation or measurement height requires different locations.

A five-parameter name does not identify a fixed set of weather measurements. Some compact weather instruments combine wind speed, wind direction, temperature, humidity and pressure. The NiuBoL NBL-W-THPLC instead combines temperature, humidity, pressure, illuminance and carbon dioxide. Comparing two devices only by the phrase "5-in-1" can therefore leave a project without a required channel.
For an integrator, the attraction is practical: one mounting assembly, one supply connection and one serial measurement point. A PLC, RTU or data logger can retrieve the five values together rather than collect five separate transmitters. This arrangement is useful for a greenhouse climate reference, an environmental recording point or a building monitoring installation where the required exposure is similar.
The channels still have different sensing behavior. Temperature follows heat exchange between the sensing element and surrounding air. Relative humidity describes water-vapor conditions relative to saturation at that temperature. Pressure represents local atmospheric pressure. The illuminance channel uses a light-sensitive detector weighted for visible-light measurement. CO2 is reported as a gas concentration in ppm. Combining them does not make their response times or uncertainties identical.
The white louvered enclosure reduces direct radiation loading on the air-sensing elements while allowing air to move through the shield. It is not an air conditioner. Heat from a nearby wall, a poorly ventilated corner or hot equipment can still bias the air entering it. A clean shield and open air paths matter because a sensor can continue returning plausible numbers after its exposure has deteriorated.
Illuminance creates a different siting requirement. The light-sensing surface needs an unobstructed view appropriate to the measurement, whereas the air elements need shielding. Do not solve a high temperature reading by placing the whole instrument under an opaque cover: that changes the light measurement. Position the assembly according to the mounting arrangement, then check both air circulation and shading across the working day.

A complete station may add wind, rain and radiation instruments around the integrated sensor. Those are separate measurements, not hidden functions of the five-channel housing. Keep mounting arms, solar panels and overhead structures from casting predictable shadows over the light channel. A photograph of a complete station is a configuration example, not a claim that every illustrated component is included.
The following values apply to the five-channel configuration. Accuracy and resolution are separate specifications: a fine display increment does not reduce the uncertainty of a measurement. Keep the ordered supply and output version in the purchase description rather than assuming any voltage or analog output is interchangeable.
| Channel or interface | Specification | Meaning for integration |
|---|---|---|
| Air temperature | -50 to 100 degrees C; accuracy +/-0.5 degrees C; resolution 0.1 degree C | The measurement range is not the complete instrument operating-temperature rating. |
| Relative humidity | 0-100% RH; accuracy +/-5% RH; resolution 0.1% RH | Small decimal changes are not proof of equally small moisture changes. |
| Atmospheric pressure | 10-1100 hPa; accuracy +/-0.3 hPa; resolution 0.1 hPa | Store local pressure separately from any sea-level-corrected value. |
| Illuminance | 0-200000 lux; accuracy +/-7%; resolution 10 lux | This is visible-light illuminance, not a direct PAR or solar-energy channel. |
| CO2 | 0-2000 ppm; accuracy +/-(40 ppm + 2% full scale); resolution 1 ppm | At this full scale the stated accuracy expression is +/-80 ppm, not +/-1 ppm. |
| Supply and output | 12 VDC or 24 VDC supply options; RS485 | Select and check the actual version before connecting power. |
| Operating environment | -50 to 80 degrees C; 0-100% RH | A humidity range does not by itself establish suitability for continuous condensation or chemical spray. |
| Serial settings | 9600 baud; 8 data bits; no parity; 1 or 2 stop bits; minimum communication interval 1000 ms | Match the delivered setting and avoid polling faster than the supported interval. |
For the 0-2000 ppm CO2 range, 2% of full scale is 40 ppm; adding the fixed 40 ppm term gives 80 ppm. A control scheme that reacts to every 1 ppm change would mistake display resolution for control capability. Allow for measurement uncertainty, spatial variation and process response when selecting an alarm band or control dead band.
Power consumption, ingress rating and cable jacket material must be established for the ordered assembly where they affect outdoor exposure or power sizing. Do not substitute a generic weather-sensor rating. Likewise, alternative current or voltage outputs require confirmation of the number of channels, their wiring and their scales; RS485 availability does not imply five analog outputs are included.

The normal measurement transaction uses Modbus function 03 to read five registers starting at address 0000. The five returned words represent temperature, humidity, pressure, illuminance and CO2 in that order. A valid CRC confirms frame integrity; it does not confirm that the receiving application has assigned the right units to each word.
Apply the channel scale individually. Positive temperature, humidity and pressure examples use a factor of 0.1; illuminance uses a factor of 10 lux; CO2 uses a factor of 1 ppm. For example, hexadecimal 00 FF is decimal 255 and represents 25.5 degrees C on the temperature channel. Hexadecimal 02 8F is decimal 655: on the humidity channel it represents 65.5% RH, while on the CO2 channel the same word represents 655 ppm. Do not copy a displayed example value without checking its conversion.
Confirm negative-temperature encoding before commissioning a freezing-weather installation. Also verify the actual address-setting procedure rather than assuming every configuration command is a conventional Modbus register write. Configure one unit at a time on a bench, assign unique operating addresses, and then connect the shared bus. Keep the acquisition timestamp and communication status with the five readings.
RS485 industrial compatibility depends on the electrical network as well as the protocol. Use an appropriate twisted pair, follow the transceiver's reference and shielding requirements, and apply termination at the bus ends where required. Multiple devices need a bus topology, not arbitrary long branches. There is no unconditional cable-distance guarantee independent of cable, baud rate, interference and grounding.
In a greenhouse, a combined temperature humidity pressure illuminance CO2 sensor can provide a local climate record with fewer field terminations. However, a shaded canopy, a CO2 injection pipe and a ventilation inlet are different environments. Use a representative air point, away from concentrated gas discharge, and decide whether lighting requires a separate crop-level quantum sensor.
For building environmental monitoring, the five channels can be logged with a PLC or building controller that supports the actual register map. Choose the occupied or process zone deliberately; a device mounted next to a warm control panel is not a room reference. A general environmental CO2 channel should not be treated as a certified life-safety gas alarm.
For outdoor environmental recording, the shared housing can reduce mounting and cable work. It cannot replace a wind instrument, a rain gauge or a pyranometer. It is also not a turbulence instrument: reading five registers together does not establish high-frequency synchronization suitable for eddy-covariance or energy-flux calculations.

If temperature rises on sunny afternoons while nearby references do not, inspect radiation exposure, reflected heat and airflow first. If humidity becomes unresponsive after wetting, examine condensation and contamination rather than repeatedly changing the calibration. If illuminance stays at zero in daylight, inspect for blockage and then compare raw register values with the application display.
Persistent CO2 disagreement needs a reference comparison under comparable conditions. Do not assume automatic baseline correction is enabled or appropriate. A continuously enriched greenhouse may never reach the background condition required by a baseline algorithm. Use the agreed calibration procedure and reference gas or instrument; do not open an optical chamber, apply solvents or force a zero adjustment as a routine troubleshooting step.
To specify the NBL-W-THPLC integrated environmental sensor, send the location, expected CO2 range, supply version, controller and intended light measurement. If the application needs PPFD, wind or rainfall, identify those as additional channels. This lets NiuBoL propose a configuration without presenting unlike measurements as equivalents.

No. This configuration measures temperature, humidity, pressure, illuminance and CO2. A five-in-one ultrasonic weather sensor may have a different channel combination. Match the parameter list, not just the number in the product name.
Not directly. Lux describes visible light with human-eye weighting. Crop lighting commonly uses PPFD in micromoles per square meter per second. A reliable conversion depends on the light spectrum; a fixed lux-to-PPFD factor is not valid across daylight and different lamps.
They can be retrieved in one read transaction, which simplifies record alignment. That does not prove identical internal sampling times or sensor response. Do not specify nanosecond synchronization or high-frequency flux measurement on that basis.
No. The temperature channel range is -50 to 100 degrees C, while the instrument operating range is -50 to 80 degrees C. The complete assembly must remain within its operating conditions even if a measurement field has a wider numerical range.
Yes, if its serial port and software support the delivered settings, function 03 read and channel scales. Check a known value on each channel, verify negative-temperature handling where relevant, and test timeout behavior before connecting control logic.
No. Digital transmission avoids some analog scaling issues but does not remove contamination, drift or reference-comparison requirements. Establish checks for the application and do not enable a CO2 baseline routine without confirming how it operates.
Include the selected power version, cable length, installation accessories and required controller connection. Request the applicable interface map and calibration options. A five-channel sensor quotation should not silently include assumptions about a complete station or cloud service.
A 5-in-1 environmental sensor is useful when five compatible measurements share a suitable location and serial connection. For the NBL-W-THPLC, the decisive checks are channel identity, CO2 uncertainty, light-measurement purpose, exposure and register scaling. Separate sensors remain the appropriate choice when those requirements cannot be met at one point.
NBL-W-THPLC-5in1-Temperature-Humidity-Pressure-Illumination-CO2-Sensor-data-sheet.pdf
Prev:Water Safety Guardian: NiuBoL Ammonia Nitrogen Sensor Working Principle, Price & Selection Guide
Next:Ultrasonic Anemometer North Alignment: Reference Marks and Heading Offsets
Related recommendations
Sensors & Weather Stations Catalog
Agriculture Sensors and Weather Stations Catalog-NiuBoL.pdf
Weather Stations Catalog-NiuBoL.pdf
Agriculture Sensors Catalog-NiuBoL.pdf
Water Quality Sensor Catalog-NiuBoL.pdf
Related products
Combined air temperature and relative humidity sensor
TDR Soil Moisture & Temperature Sensor for irrigation| RS485 |4-20mA| NBL-S-THR
Soil pH sensor RS485 soil Testing instrument soil ph meter for agriculture |NBL-S-PH
Wind Speed sensor Output Modbus/RS485/Analog/0-5V/4-20mA
Tipping bucket rain gauge for weather monitoring auto rainfall sensor RS485/Outdoor/stainless steel
Pyranometer Solar Radiation Sensor 4-20mA/RS485
Screenshot, WhatsApp to identify the QR code
WhatsApp number:+8615367865107
(Click on WhatsApp to copy and add friends)